ALARMS - Quantity Surveying Practices

Wednesday, September 7, 2011

ALARMS

This can be identified as one of the key feature of the IBMS and main purpose is when an abnormality occurs the system responds by means of alarm notifications as specified in the alarm configuration. Basically four common types can be recognized as follows,

§ Out of range

§ Floating limit

§ Change of state

§ Command failure

Both out of range and floating limit alarm types monitored only analog value such as temperature, floor rate etc…and change of state and command failure types monitored only digital values.

Alarms and Warnings

The BMS shall include an Alarm Log, and shall be capable of recording when an alarm condition starts, when the alarm is acknowledged by whom the alarm is acknowledged, and when the alarm condition is removed.

Critical Alarms - Insert specific Critical Alarm action scheme here and it will take action via interlocks or operator procedural response to shut the equipment down and notify the operator of the conditions. The operator will be required to recognize the alarm before the alarm can be reset and the system restarted. Once the alarm is reset, the operator may restart the system.

Informational Messages will notify the operator and take no further action and the equipment will have the following critical alarms and warnings

BMS alarms

informational message

alarm

response

critical

Informational massages

Interlocks

Operator procedural

Zone X High Temperature

X

X

Control Platform Communication Watchdog

X

X

Control Power Fault

X

X

Main Instrument Air Fault

X

X

Zone X Low Temperature

X

X

Zone X Low Diff. Pressure

X

X

Zone X High RH

X

X

Motor Faults

X

X

Control platform battery low warning

X

The list of critical alarms in the table is not intended to be a comprehensive list of all alarms for the system.

For a standard equipment type application, request the supplier to submit the complete alarm list and differentiate between critical and non-critical alarms. Consider documenting how “critical and non-critical” criterions were determined.

Alarms related to the Air- conditioning system

Alarms for HVAC

EQUIPMENT

ALARM

SET POINTS

Chiller system

Compressor fault

No

Failure of the compressor

No

Failure of the condenser water pump

No

CHW evaporate low flow Alarm

Chilled water flow rate set points

Chillers trip alarm

No

Exceed acceptable chilled water inlet temperature

Chilled water inlet temperature set points

Exceed acceptable chilled water out temperature

Chilled water out temperature set points

Exceed acceptable condenser water in temp.

Condenser water in temperature set points

Exceed acceptable condenser water out temp.

Condenser water out temperature set points

Oil pressure exceed the acceptable range

Oil pressure set points

Oil pressure below the acceptable range

Oil pressure set points

Oil temperature exceed adequate range

Oil temperature set points

Oil temperature less than the acceptable level

Oil temperature set points

Suction pressure exceed the acceptable pressure (bar)

Suction pressure temperature set points

Chiller system

Suction pressure less than the acceptable level

Suction pressure temperature set points

Cooling tower fan failure

No

Air Handling Units (AHU)

Failure of the AHU supply fan

No

Failure of the AHU return fan

No

Supply air temperature exceed or less than the temperature set points

AHU supply air temperature set points

Temperature of the room exceed or less than required room temperature

AHU room temperature set points

AHU dirty filter

No

AHU fan trip due to overload

No

Smoke detector trip alarm

No

Fan Coil Units (FCU)

Failure of the FCU fan

No

FCU fan trip

No

chilled water in and out temperature exceed or less than acceptable temperature

Chilled water in and out temperature set points

Supply and return air temperature exceed acceptable temperature range

Supply and return air t temperature set points

No comments:

Post a Comment