This can be identified as one of the key feature of the IBMS and main purpose is when an abnormality occurs the system responds by means of alarm notifications as specified in the alarm configuration. Basically four common types can be recognized as follows,
§ Out of range
§ Floating limit
§ Change of state
§ Command failure
Both out of range and floating limit alarm types monitored only analog value such as temperature, floor rate etc…and change of state and command failure types monitored only digital values.
Alarms and Warnings
The BMS shall include an Alarm Log, and shall be capable of recording when an alarm condition starts, when the alarm is acknowledged by whom the alarm is acknowledged, and when the alarm condition is removed.
Critical Alarms - Insert specific Critical Alarm action scheme here and it will take action via interlocks or operator procedural response to shut the equipment down and notify the operator of the conditions. The operator will be required to recognize the alarm before the alarm can be reset and the system restarted. Once the alarm is reset, the operator may restart the system.
Informational Messages will notify the operator and take no further action and the equipment will have the following critical alarms and warnings
informational message | alarm | response | ||
| critical | Informational massages | Interlocks | Operator procedural |
Zone X High Temperature
| X |
| X |
|
Control Platform Communication Watchdog
| X |
| X |
|
Control Power Fault
| X |
| X |
|
Main Instrument Air Fault
| X |
| X |
|
Zone X Low Temperature
| X |
|
| X |
Zone X Low Diff. Pressure
| X |
|
| X |
Zone X High RH
| X |
| X |
|
Motor Faults
| X |
| X |
|
Control platform battery low warning |
| X |
|
|
The list of critical alarms in the table is not intended to be a comprehensive list of all alarms for the system.
For a standard equipment type application, request the supplier to submit the complete alarm list and differentiate between critical and non-critical alarms. Consider documenting how “critical and non-critical” criterions were determined.
Alarms related to the Air- conditioning system
EQUIPMENT | ALARM | SET POINTS |
Chiller system | Compressor fault | No
|
Failure of the compressor | No
| |
Failure of the condenser water pump | No
| |
CHW evaporate low flow Alarm | Chilled water flow rate set points | |
Chillers trip alarm
| No
| |
Exceed acceptable chilled water inlet temperature | Chilled water inlet temperature set points | |
Exceed acceptable chilled water out temperature | Chilled water out temperature set points | |
Exceed acceptable condenser water in temp. | Condenser water in temperature set points | |
Exceed acceptable condenser water out temp. | Condenser water out temperature set points | |
Oil pressure exceed the acceptable range | Oil pressure set points | |
Oil pressure below the acceptable range | Oil pressure set points | |
Oil temperature exceed adequate range | Oil temperature set points | |
Oil temperature less than the acceptable level | Oil temperature set points | |
Suction pressure exceed the acceptable pressure (bar) | Suction pressure temperature set points | |
Chiller system | Suction pressure less than the acceptable level | Suction pressure temperature set points |
Cooling tower fan failure | No | |
|
| |
Air Handling Units (AHU) | Failure of the AHU supply fan | No
|
Failure of the AHU return fan | No
| |
Supply air temperature exceed or less than the temperature set points | AHU supply air temperature set points | |
Temperature of the room exceed or less than required room temperature | AHU room temperature set points | |
AHU dirty filter | No
| |
AHU fan trip due to overload | No
| |
Smoke detector trip alarm | No
| |
|
| |
Fan Coil Units (FCU) | Failure of the FCU fan | No |
FCU fan trip | No | |
chilled water in and out temperature exceed or less than acceptable temperature | Chilled water in and out temperature set points | |
Supply and return air temperature exceed acceptable temperature range | Supply and return air t temperature set points |
No comments:
Post a Comment